23kW Brewery Glycol Chiller (10 to 14 BBL) - LPA 16 BT

Features

Air cooled packaged glycol chiller designed for brewery cooling, including:

  • Highly energy efficient, low noise, hermetic scroll compressor
  • Refrigerant – R410a
  • Electronic expansion valve
  • Integral high performance 2.3 Bar pump
  • Integral pressurised/closed loop buffer tank
  • Suitable for indoor or outdoor siting
  • Three phase power supply

Description

Model LPA 16 BT
Cooling Duty @ -40C Fluid, 300C Ambient 11.3 kW1
Cooling Duty @ 150C Fluid, 300C Ambient 19.6 kW1
Settable Temperature Range -40C to +150C
Refrigerant R410a
Refrigerant Charge 5kg
Fluid Water/Glycol 30%
Fluid Flow Rate 1,200 to 4,200 Litres/Hour2
Ambient Air Temperature 300C1
Internal Pump Maximum Pressure 2.3 Bar2
Internal Pressurised Tank Capacity 60 Litres
Connection Sizes 1” BSP
Power 400V/3Ph/50Hz
Full Load Amps 16 Amps
Dimensions (mm) 1,323 (H) x 1,245 (L) x 419 (W)
Net Weight 212 Kg3
Suitable for Indoor or Outdoor Siting Fully Weatherproofed

1 Correction Factors, Page 5. 2 Pump Performance Graph, Page 5. 3 Including Packaging and Refrigerant, Tank Empty. 4 Due to the continuous development of our products, all information is subject to change without notice.