134kW Brewery Glycol Chiller (24 to 36 BBL) - Domino SEA 1115 ZC

Features

Fully Compliant with EcoDesign EER Lot 21 (Tier 2) 2021 (ERP21) European energy efficiency regulations.

Air cooled packaged glycol chiller designed for brewery cooling, including:

  • Highly energy efficient, low noise, dual hermetic scroll compressors
  • Refrigerant – R410a
  • Electronic expansion valve
  • Integral high pressure 3.5 Bar dual pumpset
  • Integral pressurised/closed loop buffer tank
  • Suitable for outdoor siting
  • Three phase power supply

Description

Model Domino SEA 1115 ZC
Cooling Duty 134.5 kW2 / 70.7 kW3
Settable Temperature Range -40C to +150C
Refrigerant / Refrigerant Charge R410a / 13 kg
Fluid Water/Glycol 30%
Fluid Flow Rate4 24,4102 / 12,7703 Litres/Hour
Internal Pump Maximum Pressure 3.5 Bar4
Internal Pressurised Tank Capacity 120 Litres
Connection Sizes 2.5″ Victaulic
Power 400V/3Ph/50Hz
Full Load Amps 108.8 Amps5
Full Load Power 37.3 kW2 / 33.3 kW3
Dimensions (mm) 2,354 (H) x 2,979 (L) x 1,004 (W)
Net Weight 827 Kg6
Suitable for Indoor or Outdoor Siting Fully Weatherproofed

Nominal Performance – See Data, Page 5. 15oC / 20oC Fluid, 30oC Ambient, 30% Glycol. -4oC / +1oC Fluid, 30oC Ambient, 30% Glycol. Run & Standby Pumps with Optional Inverter Drive. Pump Performance Graph, Page 4. Maximum Starting Current: 215 Amps. Including Packaging and Refrigerant, Tank Empty. Due to the continuous development of our products, all information is subject to change without notice. Data Sheet V1.11.